Load Sensor Input

Bridge Voltage 2.5 V / 5 V / 10 V ±10 % (30 mA maximum, remote sense can be used)
Signal input range Strain gauge sensor –3.2 mV/V to 3.2 mV/V
Calibration Calibration range 0.1 mV/V to 3.2 mV/V
Calibration method Equivalent Input / Actual Load / TEDS
Linearization function* Five-point tracking
Accuracy Linearity Within 0.01 % FS ±1 digit (when input is 3.2 mV/V)
Zero drift Within 0.5 µV/°C (Input conversion value)
Gain drift Within 0.005 % FS/°C
Filter Low pass OFF/3/10/30/100/300/1000 Hz (Digital filter, –6 dB/oct)
Moving average OFF / 2–2048 times
Auto digital Only digital value display (constant judgment)
A/D conversion Sampling rate 5000 Hz, 25 kHz
Resolution 24 bit (binary)
TEDS function IEEE 1451.4 Class 2 mix mode interface

Displacement Sensor Input (Pulse)

Pulse type A/B phase or A phase, differential square wave
(RS-422 conformance)
Maximum input frequency 2 MHz
Maximum count value 15,000,000
Calibration method Equivalent Input / Actual Load
Moving average filter OFF / 2–2048 times
Power supply for sensor driving 5 V (±10 %), 500 mA max.

Displacement Sensor Input (Voltage)

Input voltage range ±5.2 V
Calibration Calibration range 0–5.2 V
Calibration method Equivalent Input / Actual Load
Accuracy Linearity Within 0.01% FS ±1 digit (input ≥3.3 V)
Zero drift Within 0.005% FS/°C
Gain drift Within 0.02% FS/°C
Filter Low pass OFF/10/30/100/300 Hz (–6 dB/oct)
Moving average OFF / 2–2048 times
A/D conversion Resolution 24 bit (binary)
Power supply for sensor 12 V (±10%), 250 mA max.

Device Settings

Power supply DC 24V (±10%) 13 W, AC 100–240 V (AC adapter is optional)
Environment Temperature 0–40 °C (operation)
–20 °C to 60 °C (storage)
Humidity 85% RH or less (without condensation)
Dimensions, Weight Approx. 114 mm × 96 mm x 140 mm (without protrusions), About 960 g
Applicable standards EMC FCC (class A, to be scheduled)
Safety CE, UL (to be scheduled)
Display 4.3/inch LCD color resistive touch panel
Display range –32,000 to +32,000
Display Language English / Japanese / Chinese* / Korean*
Screen Digital Load Value, Waveform, Archive Data, Settings
Waveform X-axis Time 80 ms, 170 ms, 400ms, 800ms, 2 s, 4 s, 10 s, 30 s, 60 s, 120 s
Displacement 2000, 4000, 6000, 8000, 10000, 15000, 20000, 30000
Y-axis Load (STD) / Load and displacement (biaxially)
Comparison waveform Band judgment Offset reference band / Designated value band
Multi-zone judgment Up to 5 judgment zones can be set by device or external signal
Comparison judgment Load: HH / HI / OK / LO / LL
Displacement: HI / OK / LO
Hold setting Constant comparison, sampling, peak, bottom, peak to peak, maximum/minimum, inflection point and average value
Audible Beep Sounding when judgments are not OK (switchable on/off)
Measurement work settings Number of works 16 (work can be copied)
Switching External input signal / manual
Data recording Built-in memory (up to 70) or SD cards
D/A converter Output range Isolated, current: 4–20 mA, voltage: –10 V to +10 V)
Conversion rate Same as A/D converting rate
Resolution current output: about 1/43000, voltage output: about 1/59000 (when set to ±10 V)
Impedance 350 Ω or less (current output) / 2 kΩ or more (voltage output)
Communication interface RS-232C (D-sub 9-pin), USB
Control input/output signal (photocoupler insulation) Input signal Differential pulse displacement sensor (A phase, B phase), backlight On/Off, touchpanel lock, reset, work select, hold zone select, clear, judgment on/off, measurement start/end, preset displacement, digital zero
*Signals are input when shorted/opened (contact or non-contact (transistor, TTL open collector)) between any input terminal and the COM terminal.
Output signal Load judgement (HH/HI/OK/LO/LL), displacement judgment (HI/OK/LO), load cell abnormal, measurement completed, trigger (1, 2)
*NPN open collector (sync type)
*Maximum current: 20 mA, voltage: 30 V
Check functions Load cell check (static strain/nterruption detection), contact terminal check
Date and time setting Date (YYYY/MM/DD) and time can be set
Recording media SD/SDHC card (2–32 GB, Class 10 recommended)